Governor Model: IEESGO and IEESGOD
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < T3 < Mult*TimeStep then T3 = Mult*TimeStep
- If 0.0 < T1 < 0.5*Mult*TimeStep then T1 = 0, ElseIf 0.5*Mult*TimeStep < T1 < Mult*TimeStep then T1 = Mult*TimeStep
- If 0.0 < T4 < 0.5*Mult*TimeStep then T4 = 0, ElseIf 0.5*Mult*TimeStep < T4 < Mult*TimeStep then T4 = Mult*TimeStep
- If 0.0 < T5 < 0.5*Mult*TimeStep then T5 = 0, ElseIf 0.5*Mult*TimeStep < T5 < Mult*TimeStep then T5 = Mult*TimeStep
- If 0.0 < T6 < 0.5*Mult*TimeStep then T6 = 0, ElseIf 0.5*Mult*TimeStep < T6 < Mult*TimeStep then T6 = Mult*TimeStep
- If Pmax < Pmin then swap the values.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Pmech > Pmax , then Pmax = Pmech or if Pmech < Pmin , then Pmin = Pmech
Model Equations and/or Block Diagrams
Parameters for IEESGO:
| T1 | Controller lag time constant, sec |
| T2 | Controller lead time compensation, sec |
| T3 | Governor lag time constant, sec |
| T4 | Delay due to steam inlet volumes associated with steam chest and inlet piping, sec |
| T5 | Reheater delay including hot and cold leads, sec |
| T6 | Delay due to IP-LP turbine, crossover pipes, and LP end hoods, sec |
| K1 | 1/pu unit regulation |
| K2 | Fraction |
| K3 | Fraction |
| Pmax | Upper power limit (pu) |
| Pmin | Lower power unit (pu) |
Parameters for IEESGOD:
| T1 | Controller lag time constant, sec |
| T2 | Controller lead time compensation, sec |
| T3 | Governor lag time constant, sec |
| T4 | Delay due to steam inlet volumes associated with steam chest and inlet piping, sec |
| T5 | Reheater delay including hot and cold leads, sec |
| T6 | Delay due to IP-LP turbine, crossover pipes, and LP end hoods, sec |
| K1 | 1/pu unit regulation |
| K2 | Fraction |
| K3 | Fraction |
| Pmax | Upper power limit (pu) |
| Pmin | Lower power unit (pu) |
| dbH | Deadband High (pu) |
| dbL | Deadband Low (pu) |
| Trate | Turbine rating, MW |